Goodman · Furnace troubleshooting

Furnace in lockout - how to reset it

Goodman/Amana *MES9 single-stage

What is going on

The furnace has stopped after its ignition retries and the control is flashing 1 on the LED. That is a lockout, and resetting it only clears the symptom, not the cause. Know the reset methods, but find out why it failed to light. Never bypass a safety to force it to run.

Likely causes

  • Ignition failed three times (see 1 flash)

Check in this order

  1. Turn the thermostat call off for more than 5 seconds and less than 20 seconds, then call for heat again.
  2. Or turn off the furnace disconnect for at least 5 seconds.
  3. The control also resets by itself an hour after lockout.
  4. If it keeps locking out, fix the cause with the 1 flash steps.
  5. LED flash codes clear when power to the control is cut, including by the door switch, so note the code before opening the door.
  6. If it relocks repeatedly, stop resetting and have a licensed technician diagnose the gas and ignition system.

Applies to: GMES9, GCES9, AMES9, ACES9, VMES9, VCES9 (single stage, 92% and 96%)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman Service and Troubleshooting GMES9*/GCES9*/AMES9*/ACES9*/VMES9*/VCES9* (RS6612016r3) , Heating - Abnormal Operation p.26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.