Goodman · Furnace troubleshooting
Flashback at ignition or burner shutoff
What is going on
Flashback is when the flame burns back into the burner venturi because the burning speed is faster than the gas and air coming out of the port. You see it at ignition, after the burners warm up, or at shutoff as a pop when the flame goes out. In my experience gas pressure and a shifted burner are the usual culprits. Delayed ignition can look the same from the outside, so work out which one you actually have before you start changing parts.
Likely causes
- Improper gas pressure
- Burner misalignment
- Improper orifice size or obstructed orifice
- Dirty or rusted burner ports disturbing the gas-air mix
Check in this order
- Check gas pressure and adjust to rating plate values (see gas pressure checks). Gas work is for a qualified gas technician
- Check burner alignment and replace the burner if needed
- Check the orifice for obstruction and correct size
- Watch the burner light and shut off to see exactly when the pop happens
- Inspect burner ports and clean out debris with power and gas off
- Recheck flame pattern after repairs
Applies to: Main burners
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service manual, p. 53. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.