Goodman · Furnace troubleshooting

Flame sensor microamp check

A/GMVC96A/GCVC96

What is going on

Flame current is measured in series with the sensor. The integrated ignition control needs 1 to 4 microamps to prove flame. Contaminated fuel or air can coat the sensor and reduce the signal.

Likely causes

  • High resistance wiring connections
  • Sensor-to-burner gap wrong
  • Dirty flame sensor
  • Poor grounding
  • Failed ignition control (no reading after continuity check)

Check in this order

  1. Shut off power and disconnect the flame sensor wire from the sensor.
  2. Connect a micro-amp meter in series between the wire and sensor terminal, positive to the wire and negative to the sensor.
  3. Restore power and start a heating cycle.
  4. Read the micro-amp value once flame is established. The hot surface ignitor turns off after proof of flame.
  5. If the reading is below 1 microamp, check wiring, the sensor-to-burner gap, sensor cleanliness and grounding.
  6. If there is no reading, check continuity of all components, then replace the ignition control if good.
  7. Clean a coated sensor with steel wool.

Applies to: Flame sensor and ignition control

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service manual, p. 55. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.