Goodman · Furnace troubleshooting
Flame sensor microamp check
What is going on
Flame current is measured in series with the sensor. The integrated ignition control needs 1 to 4 microamps to prove flame. Contaminated fuel or air can coat the sensor and reduce the signal.
Likely causes
- High resistance wiring connections
- Sensor-to-burner gap wrong
- Dirty flame sensor
- Poor grounding
- Failed ignition control (no reading after continuity check)
Check in this order
- Shut off power and disconnect the flame sensor wire from the sensor.
- Connect a micro-amp meter in series between the wire and sensor terminal, positive to the wire and negative to the sensor.
- Restore power and start a heating cycle.
- Read the micro-amp value once flame is established. The hot surface ignitor turns off after proof of flame.
- If the reading is below 1 microamp, check wiring, the sensor-to-burner gap, sensor cleanliness and grounding.
- If there is no reading, check continuity of all components, then replace the ignition control if good.
- Clean a coated sensor with steel wool.
Applies to: Flame sensor and ignition control
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service manual, p. 55. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.