Goodman · Furnace troubleshooting
Flame detected when no flame should be present
What is going on
Control sees flame with no call for heat, so the inducer and circulator blower keep running.
Likely causes
- Short to ground in the flame sense circuit, which looks like flame to the control
- Lingering burner flame after the gas should be off
- Slow closing gas valve
Check in this order
- Power off before any repair.
- Look at the burners with the thermostat satisfied. Flame still there means gas is passing or lingering.
- Correct the short at the flame sensor or in its wiring, because the wiring can ground out on the chassis.
- Verify proper operation of the gas valve and that it closes fully and promptly.
- A gas valve that will not shut off goes to a licensed gas tech.
- Retest through a few full cycles.
Applies to: 34.5 in chassis gas furnaces
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 Service and Troubleshooting, p. 61. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.