Goodman · Furnace troubleshooting

Customer bundle: auxiliary condensate switch wiring

34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Aux alarm input on the GMVC96 family control. It's meant for a condensate switch, and compatible CO2 sensors or fire alarms can use it too. Switch is normally closed. Opens on high water, control shuts the furnace down.

Likely causes

  • Condensate switch open because the drain is backed up
  • Switch wired to the wrong terminal or wire loose
  • Switch itself failed open

Check in this order

  1. Confirm the switch is landed on the Condensate terminal.
  2. Confirm the switch is normally closed. It opens when the evaporator base pan water level is too high.
  3. If the switch is open, check the condensate drain first. Look for a plugged line or trap.
  4. Clear the blockage, let the pan drain, then see if the switch closes again.
  5. With power off, check the switch for continuity by meter. Open with a dry pan means a bad switch.
  6. Check the connections at the terminal for looseness.

Applies to: Furnace with Aux alarm input

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.