Goodman · Furnace troubleshooting
Control display blank, furnace dead - Goodman/Amana 9-speed ECM furnaces
What is going on
The furnace does nothing and the 7-segment display on the integrated control module shows nothing (the troubleshooting chart lists this as LED status 'None').
Likely causes
- No 115 V power to the furnace or no 24 V to the control
- Blown fuse or tripped breaker
- Failed integrated control module
Check in this order
- Warning: line voltage present - measure carefully.
- Check that 115 VAC power reaches the furnace: breaker, service switch and the blower door interlock switch (door must be closed or the switch held in).
- Measure 115 VAC at the control board line terminals and 24 VAC at the transformer secondary.
- If 24 VAC is present at the transformer but missing at R-C, the board fuse is open - find and fix the low-voltage short, then replace the fuse.
- Correct whatever tripped the breaker or blew the fuse before resetting.
- Power and fuse good but still no display replace the integrated control module.
- Note opening the blower door without holding the door switch closed clears the stored fault - read the fault history (L6F) through the sight glass first.
Applies to: Goodman/Amana/GMC gas furnaces, 9-speed ECM, 7-segment control. Two-stage 96%: AC9C96, AM9C96, GC9C96, GM9C96. Single stage 80%: VC9S80, VM9S80, AC9S80, AM9S80, GC9S80, GM9S80. Single stage 92/96%: VC9S96, VM9S96, AC9S96, AM9S96, AM9S92, GC9S96, GM9S96, GM9S92
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman RS6612022r1 (GM9S92/GM9S96/GC9S96 service), 1 Stage Troubleshooting Codes, p.29-30; Goodman RS6621008r2 (GM9S80 service), p.32-33; Goodman RS6612020r1 (GM9C96 service), 2 Stage Troubleshooting Codes, p.35-36; Checking Integrated Ignition Control Boards p.25 (RS6612022r1). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.