Goodman · Furnace troubleshooting
ComfortNet data line check - Goodman *MVC95/*CVC9
What is going on
How to check the two communication wires (data 1 and data 2) when the furnace, thermostat and outdoor unit are not talking.
Likely causes
- Dip switches set wrong
- Data wires reversed, broken or shorted
- Wire run too long
Check in this order
- With power on, measure data 1 to C about 2.6 V DC. Data 2 to C: about 2.3 V DC. Data 1 to data 2: about 0.2-0.6 V DC.
- With all bias and termination dip switches ON you should read over 2.5 V (1-C), under 2.5 V (2-C) and over 0.2 V (1-2).
- On the furnace control, BIAS switches 1 and 2 and TERM switch 3 should all be ON. The outdoor unit TERM switches should also be ON.
- Reading 5 V / 0 V / 5 V or 0 / 0 / 0 points to a switch set wrong or a wiring fault. Fix the switch or wiring and retest.
- Use 18 AWG thermostat wire, max 100 ft from furnace to outdoor unit or to the thermostat.
- Press the learn button for about 2 seconds to reset the network after any change.
Applies to: GMVC95/AMVC95 upflow and *CVC9 counterflow two-stage furnaces
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman *CVC9/95 & *MVC95 Installation Instructions IO-341D (08/2010), Network Troubleshooting p.46-47; ComfortNet Wiring p.43. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.