Clocking a gas meter

ACVC96AMVC96GCVC96GMVC96

What is going on

Clocking the meter tells you how much gas the furnace really burns, which feeds the BTU input calculation in the heating performance test. Run the furnace at 100% firing rate until it reaches steady state, usually about 15 minutes, then time one revolution of the test dial. Meters that are shared with other appliances give junk numbers, so isolate the furnace first.

Likely causes

  • Heating performance test needs an actual input figure
  • Suspected over-fire or under-fire after a gas conversion or altitude change
  • Complaints of weak heat or flame problems where manifold pressure alone is not conclusive

Check in this order

  1. Turn off all other gas appliances in the home, including water heater pilots that may cycle on, and check the meter dial is not moving
  2. Turn on the furnace and confirm it runs at 100% firing rate, not low stage
  3. Wait about 15 minutes of steady operation so the burners and heat exchanger settle
  4. Time one full revolution of the smallest dial with a stopwatch. The one cubic foot dial is used in the example
  5. Find the seconds for one revolution in the gas rate table and read CFH from the matching dial column
  6. Example 40 seconds on the 1 cu ft dial gives 90 CFH
  7. Multiply CFH by the gas heating value to get BTU/h and compare with the rating plate

Applies to: All 34.5in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 40. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.