Goodman · Furnace troubleshooting

Circulator blower motor not running when it should be

ACVC96AMVC96GCVC96GMVC96

What is going on

Circulator blower not running on a call for heat or airflow.

Likely causes

  • Loose or disconnected wiring at the circulator motor power leads, because a pulled plug is cheaper than a motor
  • Open circuit in the inductor or loose inductor wiring, on 3/4 HP and 1 HP models only
  • Failed circulator blower motor

Check in this order

  1. Power off before repair, then inspect the motor power lead connections. Tighten or correct them, since a loose lead gives no power to the motor.
  2. On 3/4 HP and 1 HP models, check for a continuous circuit through the inductor with a meter. Replace it if open or shorted.
  3. With power restored, check that line voltage reaches the motor leads on a call, since no voltage points to the control or wiring.
  4. Check the circulator blower motor and replace it if necessary.
  5. Spin the wheel by hand with power off to make sure it is free.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 62. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.