Goodman · Furnace troubleshooting

Checking unit grounding

34.5 in chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Before you trust any electronic control on this Goodman furnace, confirm it has a solid ground. The gas piping must never be used as the electrical ground, so the path has to run through the furnace ground screw and the supply wiring back to the panel. Do this check with the power off, and call a licensed electrician if the ground path is in doubt.

Likely causes

  • A missing or broken ground wire between the junction box and the panel
  • A loose or corroded ground screw connection
  • A poor connection from the neutral side to the burners, which raises the resistance reading

Check in this order

  1. Shut off the electrical power at the disconnect and confirm it is dead with a meter before touching anything.
  2. Measure resistance between the neutral (white) connection and one of the burners.
  3. Confirm the reading is 10 ohms or less.
  4. Trace the ground wire from the furnace ground screw in the junction box back to the electrical panel and confirm it is continuous.
  5. Tighten or clean any loose or corroded ground connection and recheck the reading.
  6. If the ground path cannot be proven, have a licensed electrician correct the wiring before returning the furnace to service.

Applies to: Gas furnace

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 25. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.