Goodman · Furnace troubleshooting

Check wiring

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

A visual and continuity check of the wiring on the GMVC96 family furnace. Do it with the power off and confirmed dead, since the wiring carries line voltage. Burnt or loose connections are a common hidden cause of intermittent faults, so look carefully before replacing parts.

Likely causes

  • Overheated or damaged wire insulation
  • Loose or corroded connections
  • A broken conductor that reads open on the meter

Check in this order

  1. Shut off power at the disconnect and verify with a meter that it is dead.
  2. Look for signs of overheating, damaged insulation and loose connections.
  3. Use an ohmmeter to check continuity of any wire you suspect is open.
  4. If a wire must be replaced, use AWM 105°C wire with 2/64 inch insulation of the same gauge or equivalent.
  5. Re-secure the wiring away from sharp edges and hot surfaces.
  6. Restore power and confirm the furnace runs a full cycle.

Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.