Goodman · Furnace troubleshooting

Check transformer phasing on unmarked transformers

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Some electronic boards that use flame rectification need the low voltage side to be in phase with the line side. If a transformer has no phasing marks, you have to find out yourself. Wrong phasing can stop the board working at all.

Likely causes

  • Unmarked transformer wired with the secondary reversed
  • Transformer replaced without checking phasing
  • Board with flame rectification that will not accept out-of-phase power
  • Flame sense faults appearing right after a transformer swap

Check in this order

  1. With power on, measure from the low voltage common/ground to the hot line leg
  2. About 96 V means primary and secondary are in phase
  3. About 144 V means they are out of phase, so reverse the low voltage wires
  4. The readings are approximate, so a clear gap between the two numbers is what matters
  5. Wire the furnace to match the phasing. Some transformers have phasing symbols to help identify the correct orientation
  6. Power off before changing wires, then retest and confirm the board starts normally

Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 42. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.