Check thermostat and low voltage wiring

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Decides whether a no-heat or no-cool problem is in the thermostat or the wiring, or in the furnace.

Check in this order

  1. Remove the blower compartment door and disconnect the thermostat low voltage wires at the furnace control terminals.
  2. Jumper R to W (or W1 and W2 on two-stage models) on the integrated ignition control.
  3. With power on and the door interlock closed, the induced draft motor must run and pull in the pressure switch.
  4. If the hot surface ignitor heats and the gas valve opens and the burners light, the fault is in the thermostat or wiring.
  5. With power off, check continuity of the thermostat and wiring. Repair or replace as needed.
  6. To check cooling mode, with power off jumper R to Y (or Y1/Y2) to G, then turn power on.
  7. If the blower starts and the condensing unit runs, the fault is in the thermostat or wiring.
  8. Reinstall the blower compartment door and verify operation.

Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.