Goodman · Furnace troubleshooting

Check primary limit control

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

The primary limit is a non-adjustable, automatic reset bi-metal control on the heat exchanger. It should read open only when the heat exchanger is hotter than its setting. Test it cold with the low voltage wires off.

Likely causes

  • Limit reads open while cold, meaning it has failed
  • Heat exchanger really above the limit setting because of poor airflow
  • Wrong limit fitted, with a different temperature setting
  • Loose or corroded connection at the limit terminals

Check in this order

  1. Remove the burner compartment door with power off
  2. Disconnect the low voltage wires at the limit control terminals
  3. Use an ohmmeter across the two terminals. It should read continuous unless the heat exchanger is above the limit setting
  4. If the reading does not match, replace the control
  5. Use the Primary Limit Charts in the furnace technical manual to confirm part number, temperature setting and color code
  6. If the limit trips in normal use, check the filter, registers and blower before replacing it
  7. Reinstall the burner compartment door, restore power, and verify operation

Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96 (90% furnaces)

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 47-48. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.