Goodman · Furnace troubleshooting

Check line voltage to the furnace

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Confirm the supply voltage at the junction box and at the blower while it runs.

Likely causes

  • No reading can mean open wiring, an open fuse, no power, or a faulty door interlock switch.

Check in this order

  1. Turn power off, remove the burner door, and remove the junction box cover.
  2. Turn power on with the door interlock switch engaged. Measure voltage across hot and neutral with a voltmeter.
  3. If there is no reading, check wiring, the fuse, power supply and the door interlock switch.
  4. Jumper R to G on the integrated ignition control to run the blower.
  5. With the blower running, voltage should be 115 V within plus or minus 10%.
  6. If voltage is low, check line wire size. Undersized long runs can cause low voltage. If wire size is adequate, notify the power company.
  7. Reinstall the junction box cover and service doors, then restore power and verify operation.

Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.