Goodman · Furnace troubleshooting

Check flame rollout switch

A/GMVC96A/GCVC96

What is going on

Manual reset rollout switch on the burner bracket. It opens on flame rollout, flame impingement on the heat shield or over-firing. The blower runs continuously when it opens.

Likely causes

  • Flame impingement on heat shield
  • Orifice plate out of position
  • Burners with excessive cross-over slot dimension
  • Over-firing
  • Improper orifices or gas pressure
  • Air leaking around or through the heat exchanger into the burner compartment

Check in this order

  1. Shut off power and remove the burner compartment door.
  2. Press the manual reset on the rollout switch.
  3. Remove the wires from the switch.
  4. Check continuity across the switch with an ohmmeter.
  5. If it will not close after reset, replace it.
  6. Find and correct the cause of the trip before returning to service.
  7. Reinstall the burner door and verify operation.

Applies to: 90% upflow and counterflow furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service manual, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.