Goodman · Furnace troubleshooting

Check ECM high voltage power circuits

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

This is the test for line voltage getting to the ECM blower motor through the 5-circuit power connector. Straightforward once you know the pin pairs. You will have power on while you meter, so keep your hands clear and use the right meter range. A motor can look dead when it simply isn't being fed.

Likely causes

  • No supply voltage reaching the furnace
  • A bad connection or break in the 5-circuit harness feeding the motor

Check in this order

  1. Disconnect power, then unplug the 5-circuit power connector from the ECM motor.
  2. Turn power on and measure between pins 4 and 5. It should equal the furnace supply voltage.
  3. Measure between pins 4 and 3. It should be about zero volts.
  4. Measure between pins 5 and 3. It should equal the furnace supply voltage.
  5. If there is no voltage, check the furnace supply voltage (see section S-1).
  6. Disconnect power and reconnect the 5-circuit harness.

Applies to: ECM blower motors on ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 45-46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.