Goodman · Furnace troubleshooting

Check ECM control/end bell

34.5 in. chassis ACVC96/AMVC96/GCVC96/GMVC96

What is going on

Checks the thermistor, capacitors and connector resistance in the control/end bell.

Likely causes

  • Cracked thermistor, bulging capacitors or low resistance in the connector.

Check in this order

  1. Disconnect power and wait 5 minutes for capacitors to discharge.
  2. Disconnect the motor control and motor power harnesses, then remove the blower assembly.
  3. Remove the 3 screws and separate the control/end bell from the motor. Disconnect the 3-circuit harness.
  4. Inspect the NTC thermistor. Replace the control/end bell if it is cracked or broken.
  5. Inspect the large capacitors. Replace the control/end bell if any are bulging or swollen.
  6. Measure resistance between each terminal in the 3-circuit connector. 100 kΩ or greater is good. Replace if lower.
  7. Reassemble in reverse and reinstall the blower assembly.

Applies to: ECM blower motors on ACVC96/AMVC96/GCVC96/GMVC96

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service and troubleshooting manual, p. 46. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.