Goodman · Furnace troubleshooting
Check duct static pressure
What is going on
Adds the return and supply static readings to get total external static pressure, then compares it with the blower tables.
Likely causes
- Too much static can cause insufficient airflow, high temperature rise and limit tripping.
- Too little static can overload the motor.
- Closed dampers or registers, and undersized or poorly laid out ductwork, are common causes.
Check in this order
- With clean filters installed, use a draft gauge (inclined manometer) to measure return static at the furnace inlet. This is a negative reading.
- Measure supply duct static. This is a positive reading.
- Add the two readings together for total external static pressure. Include any coil or electronic air cleaner in the total.
- Compare the total with the allowable minimum and maximum in the blower tables.
- If the total is outside the limits, check for closed dampers or registers and for ductwork problems.
Applies to: Gas furnaces ACVC96/AMVC96/GCVC96/GMVC96
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 service and troubleshooting manual, p. 46-47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.