Goodman · Furnace troubleshooting

Check blower (inducer) pressure switch

A/GMVC96A/GCVC96

What is going on

The pressure control stops combustion if venting is restricted or blocked. A/GMVC96 and A/GCVC models also have a front cover pressure switch in series with the gas valve. It blocks the valve if condensate backs up in the secondary heat exchanger.

Likely causes

  • Restricted or blocked vent pipe
  • Improperly connected or plugged condensate drain
  • Defective pressure switch

Check in this order

  1. Shut off power and remove the burner compartment door.
  2. Remove the wires from the pressure switch terminals.
  3. Disconnect the pressure hose and connect an inclined manometer through a 1/4 in. tee to the inducer tap.
  4. With an ohmmeter across the switch terminals and the inducer running, the switch should close.
  5. If it does not close, compare the negative pressure to the switch closing point.
  6. If the pressure is fine, replace the switch. If pressure is low, check the inducer and venting.

Applies to: Blower pressure switch and front cover pressure switch

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 service manual, p. 53. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.