Goodman · Furnace troubleshooting

Blower motor over or under voltage, or over temperature on power module

ACVC96AMVC96GCVC96GMVC96

What is going on

I see this one on jobs where the power to the house is flaky or the furnace sits in a hot spot. The motor shuts itself down when line voltage is too high or too low, or when the power module overheats. Check what the furnace is actually getting before blaming the motor.

Likely causes

  • High AC line voltage to the furnace
  • Low AC line voltage to the furnace, often from a loose supply connection or a weak circuit
  • High ambient temperatures around the furnace

Check in this order

  1. Check power to the furnace and verify line voltage is within the range on the furnace rating plate.
  2. Check voltage while the blower is trying to run. Low voltage that only shows under load points to a bad connection.
  3. Check the installation location requirements for ambient temperature.
  4. Turn power off before repair.
  5. Replace the motor with the correct replacement part if needed.
  6. Have a licensed electrician check the supply circuit if the voltage is out of range.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.