Blower motor horsepower mismatch
What is going on
The control checks the motor horsepower stored in its shared data set against the circulator blower motor that is actually installed. When they do not match, the control flags an error and will not run. Do not assume the motor is bad. A previous board swap with the wrong data set is just as likely. Switch off power and confirm both the motor and the data before changing anything, and never mix parts from another furnace.
Likely causes
- Incorrect circulator blower motor in furnace
- Incorrect shared data set in integrated control module
- Wrong memory card used on a previous control replacement
Check in this order
- Turn power off before repair
- Verify the circulator blower motor horsepower is the one specified for this furnace model, using the motor label and the parts list. Replace if necessary
- Verify the shared data set is correct for the model. Re-populate with the correct memory card if required
- Use the memory card for the specific model and insert it before turning power on
- Power up and let the data load, then power off and remove the card per the manual
- The error clears once shared data and motor horsepower match
- Handle the board with static precautions
Applies to: 34.5 in chassis gas furnaces
More furnace guides
- Airflow lower than demanded, furnace runs on low stage when high stage is expected
- Alternate combustion air opening (upflow or horizontal)
- Alternate vent/flue location (upflow or horizontal left)
- Annual inspection checklist
- Auxiliary limit control (location and purpose)
- Auxiliary limit switch open (blower compartment)
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.