Blower motor fails to start after 10 consecutive tries

ACVC96AMVC96GCVC96GMVC96

What is going on

Circulator blower motor tried to start ten times in a row and failed, so the furnace is down.

Likely causes

  • Obstruction in the circulator blower housing, so the wheel can't turn
  • Seized circulator blower motor bearings, because a dry bearing locks up
  • Failed circulator blower motor

Check in this order

  1. Turn power off before repair.
  2. Pull the blower and look in the housing for debris or anything jamming the wheel. Remove it.
  3. Spin the wheel and shaft by hand, since a tight or locked shaft means seized bearings.
  4. Replace the motor with the correct replacement part if it is seized or failed.
  5. Replace the wheel with the correct part if it is damaged or out of balance.
  6. Restore power and confirm the blower starts and runs smoothly.

Applies to: 34.5 in chassis gas furnaces

More furnace guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Goodman GMVC96 Service and Troubleshooting, p. 63. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.