Servicing a system with flammable refrigerant (R454B)

D5FUAAH

What is going on

General service rules for flammable refrigerant systems. Only trained, certified personnel should work on refrigerant circuits.

Check in this order

  1. Check the work area with a suitable refrigerant detector before and during work.
  2. Keep ignition sources and open flames away, and have a dry powder or CO2 extinguisher nearby for hot work.
  3. Make sure the area is ventilated during the work.
  4. Recover refrigerant into correct recovery cylinders, then purge with oxygen-free nitrogen. Do not use compressed air or oxygen.
  5. Charge by the liquid method only, avoid overfilling, and label the system when charging is complete.
  6. Check that electrical components are discharged and that earth bonding is continuous before work.
  7. Do not use a halide torch or any naked-flame leak detector.
  8. Leak test after charging and again before leaving the site.

Applies to: D5FUAAH and other R454B systems

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUAAH Owner's Manual, p. 4-6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.