Carrier · Air handler troubleshooting

Bending copper refrigerant tubing

D5FUHA

What is going on

Bends must use a properly sized tubing bender to avoid kinking. Minimum bend radius is 3.9 in (100 mm) at the middle of the tube. Do not bend more than 90 degrees or more than 3 times in one place.

Likely causes

  • Kinking or flattening the tube restricts flow and can damage it

Check in this order

  1. Use a tubing bender sized for the line.
  2. Keep the bend radius at least 3.9 in (100 mm).
  3. Do not bend more than 90 degrees.
  4. Do not bend the same tube more than 3 times.

Applies to: D5FUHA field copper lines

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHA installation instruction, p. 28-29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.