Charging, recharge test and decommissioning for flammable refrigerant

D5FSAA / D5FLAA

What is going on

Charging and recovery practice when the system is serviced or retired.

Check in this order

  1. Use only tools rated for flammable refrigerants. Keep hoses as short as possible.
  2. Keep cylinders upright. Earth the system before charging.
  3. Do not overfill. Pressure test with oxygen-free nitrogen before recharging.
  4. Leak test after charging and again before leaving the site.
  5. Before decommissioning, take an oil and refrigerant sample if analysis may be needed. Make sure power is available.
  6. Pump the system down if possible. Do not fill recovery cylinders above 80% liquid volume or above their maximum pressure.
  7. Do not charge recovered refrigerant into another system unless it is cleaned and checked.
  8. Label the unit as decommissioned and emptied. Label flammable refrigerant units as containing flammable refrigerant.

Applies to: Indoor and outdoor units using flammable refrigerant

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.