Carrier · Air handler troubleshooting

Adjust cooling or heating airflow through service codes

D5FUAA

What is going on

Airflow is changed by stepping the fan-speed offset for each mode. Code 23 sets cooling and code 25 sets heating. Use the fan performance tables for the expected results.

Check in this order

  1. Set up the remote for SERVICE mode (see the enter-service tip).
  2. Use UP and DOWN to scroll to CODE 23 (maximum cooling fan speed) for cooling changes, or CODE 25 (maximum heating fan speed) for heating changes.
  3. Press ON/OFF for 2 seconds to enter SERVICE mode for that code and change the offset.
  4. Compare the result with the fan performance table for the unit size.
  5. Exit SERVICE and INQUIRY modes.
  6. Power down the outdoor unit for 3 minutes to lock the changes.

Applies to: Vertical, Horizontal Right and Horizontal Left installations

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FUAA installation instructions, p. 49. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.