Carrier · Air handler troubleshooting
Braze connections and nitrogen pressure test
What is going on
When the air handler connection is brazed, flow nitrogen through the system while brazing, then pressure test. Insulate the suction line completely, including the outdoor unit valves. A flare-to-braze adapter may be used at the air handler.
Likely causes
- Brazing without nitrogen flow can leave oxidation inside the line set
Check in this order
- Cut and deburr the tubing to the outside diameters in the connection table.
- Set up the nitrogen apparatus and connect it to the outdoor unit so nitrogen flows while brazing.
- Braze the tubing and any fittings to get a proper seal.
- Pressurize the system with nitrogen and pressure test to a maximum of 500 psig for at least 60 minutes.
- Insulate the suction line completely, including the outdoor unit valves.
- If a flare-to-braze adapter is used, repeat the same cut, braze and test steps at the adapter.
Applies to: D5FUHA line set brazing
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHA installation instruction, p. 29. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.