Carrier · Air handler troubleshooting
Service work on a flammable refrigerant circuit
What is going on
General order of work for opening or repairing a circuit that uses flammable refrigerant (A2L).
Check in this order
- Confirm the technician holds a current refrigerant handling certificate.
- Check the area with a suitable detector before and during work.
- Keep ignition sources away and post no smoking signs.
- Keep the area open or ventilated during the work.
- Isolate the system electrically and check that capacitors are discharged.
- Recover the refrigerant into correct recovery cylinders if venting is not allowed.
- Purge with oxygen-free nitrogen. Never use compressed air or oxygen.
- Break the vacuum with nitrogen, fill to working pressure, vent, and repeat until no refrigerant remains.
- Evacuate the system before opening the circuit.
- Only open the circuit when all refrigerant is removed.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FULA installation instructions, p. 5-7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.