Carrier · Air handler troubleshooting

Service work on a flammable refrigerant circuit

D5FULA

What is going on

General order of work for opening or repairing a circuit that uses flammable refrigerant (A2L).

Check in this order

  1. Confirm the technician holds a current refrigerant handling certificate.
  2. Check the area with a suitable detector before and during work.
  3. Keep ignition sources away and post no smoking signs.
  4. Keep the area open or ventilated during the work.
  5. Isolate the system electrically and check that capacitors are discharged.
  6. Recover the refrigerant into correct recovery cylinders if venting is not allowed.
  7. Purge with oxygen-free nitrogen. Never use compressed air or oxygen.
  8. Break the vacuum with nitrogen, fill to working pressure, vent, and repeat until no refrigerant remains.
  9. Evacuate the system before opening the circuit.
  10. Only open the circuit when all refrigerant is removed.

Applies to: D5FULA crossover evaporator coil with flammable refrigerant

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FULA installation instructions, p. 5-7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.