Service precautions for flammable refrigerant systems
What is going on
Work on R454B systems requires a valid competency certificate. Follow a controlled work procedure to reduce the risk of flammable gas being present. Ventilation must continue during the work.
Check in this order
- Confirm the technician holds a current certificate for handling flammable refrigerants.
- Check the area with a refrigerant detector suitable for flammable refrigerants before and during work.
- Remove or keep away all ignition sources, including smoking. Post no-smoking signs.
- Keep a dry powder or CO2 fire extinguisher at the charging area when hot work is done.
- Ensure ventilation during the work and before opening the circuit.
- Recover refrigerant into correct cylinders before opening the circuit. Do not overfill cylinders above 80% liquid volume.
- Purge with oxygen-free nitrogen. Never use compressed air or oxygen.
- Use earthing before charging. Keep charging hoses as short as possible and cylinders upright.
- Label the equipment as containing flammable refrigerant.
Applies to: Repair, service and decommissioning of R454B systems
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHA Installation Instructions, p. 6-8. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.