Carrier · Air handler troubleshooting

Select location: separation, grounding and return air

D5FSAA / D5FLAA

What is going on

Location rules for the indoor unit, including return air and garage installs.

Check in this order

  1. Keep indoor and outdoor units, cables and wires at least 1 m (3-1/5 ft) from televisions or radios to avoid static or image distortion. This may not be enough for some appliances.
  2. Electrically ground the indoor unit per national and local electrical code.
  3. Mount on a structure that can support the unit weight.
  4. Do not install in a moist environment; moisture corrodes parts and can cause shorts.
  5. Do not install where there are corrosive gases, oil drilling, coastal salt, strong electromagnetic waves, or stored flammable materials or gas.
  6. For a garage installation, place the heating elements at least 18 in (46 cm) above the floor.
  7. Make an airtight seal between the bottom of the air handler and the return air plenum using fiberglass strips, foil tape, caulking or an equal method.
  8. Do not draw return air from a room with a gas appliance, water heater, or carbon-monoxide-producing device such as a wood fireplace.

Applies to: Indoor air handler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.