Carrier · Air handler troubleshooting
Secondary condensate pan and overflow protection
What is going on
Where water damage could occur from overflow, a secondary pan or drain line is required.
Check in this order
- Install a field-supplied external condensate pan under the whole unit and run a secondary drain line with a trap into it.
- Drain the external pan to a visible location.
- Alternatively, where local code permits, run a separate 3/4 in condensate line with a trap to a visible location.
- Install a float switch to shut the unit off if the secondary pan fills.
- Tell the owner that the unit needs service if water runs from the secondary drain or pan.
Applies to: D5FULA installs in or above living space
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FULA installation instructions, p. 24. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.