Secondary condensate pan and overflow protection

D5FULA

What is going on

Where water damage could occur from overflow, a secondary pan or drain line is required.

Check in this order

  1. Install a field-supplied external condensate pan under the whole unit and run a secondary drain line with a trap into it.
  2. Drain the external pan to a visible location.
  3. Alternatively, where local code permits, run a separate 3/4 in condensate line with a trap to a visible location.
  4. Install a float switch to shut the unit off if the secondary pan fills.
  5. Tell the owner that the unit needs service if water runs from the secondary drain or pan.

Applies to: D5FULA installs in or above living space

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FULA installation instructions, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.