Seal the return air plenum and cabinet penetrations

D5FUAA

What is going on

The unit must be airtight at the return plenum and at every pipe, wire and drain opening, so warm or unconditioned air cannot enter the cabinet.

Check in this order

  1. Set the unit on the floor over the return opening, with return duct flush with the floor. All return air must pass through the coil.
  2. Seal between the bottom of the air handler and the return plenum with fiberglass sealing strips, foil duct tape, caulk or an equivalent method.
  3. Apply sealant where the wires, refrigerant pipes and condensate pipes enter the cabinet.
  4. Seal any space around the drain line holes with duct tape or flexible sealant.
  5. Use a standard filter that meets UL900. The user supplies this filter. Ask the manufacturer if you are unsure how to select one.
  6. Do not draw return air from a room that contains a gas-fueled appliance (such as a water heater) or a carbon monoxide producing device (such as a wood fireplace).

Applies to: D5FUAA sizes 18K to 60K

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUAA installation instructions, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.