Carrier · Air handler troubleshooting

Rotate evaporator and reconnect sensors

D5FSAAD5FLAA

What is going on

Used when the unit is set up for vertical downflow. Route wires through the cabinet correctly and reseal the openings.

Check in this order

  1. Remove the evaporator and drain pan, then rotate them 180 degrees for vertical down.
  2. Adjust the mounting part positions for the unit direction.
  3. Reinstall the evaporator and drain pan.
  4. Reconnect the T1, T2, T2A and T2B sensor plugs and the electronic expansion valve (EEV), then tie up the sensor wires.
  5. Cut the foam gasket and remove the knockouts.
  6. Hook the wire into the strap and run it down through the wire slot.
  7. Put the foam gasket back over the wires.

Applies to: D5FSAA / D5FLAA air handler, vertical downflow

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSAA/D5FLAA installation manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.