Carrier · Air handler troubleshooting

Return air seal and return air source

D5FSAAD5FLAA

What is going on

The return air connection must be airtight and must not pull air from a room with a gas appliance or a combustion source.

Check in this order

  1. Seal the bottom of the air handler to the return air plenum with fiberglass strips, foil tape, caulk or an equivalent seal.
  2. Do not draw return air from a room that contains the air handler or any gas-fired appliance, such as a water heater, or a carbon monoxide source, such as a wood fireplace.
  3. Locate the return intake away from heat sources and warm or cool air sources that could change the sensed return air temperature.
  4. If return air is ducted, install the duct flush with the floor and set the unit over the opening so all return air passes through the coil.

Applies to: D5FSAA / D5FLAA air handler

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSAA/D5FLAA installation manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.