Removing refrigerant before breaking into the circuit

D5FUHA

What is going on

Use this sequence before brazing or opening the refrigerant circuit on a flammable refrigerant unit.

Check in this order

  1. Remove the refrigerant safely following local and national rules, or isolate the leaking section with shut-off valves.
  2. Evacuate the circuit.
  3. Purge the circuit with inert gas.
  4. Evacuate again.
  5. If using flame to open the circuit, keep flushing with inert gas, then open the circuit.
  6. Recover refrigerant into correct recovery cylinders if venting is not allowed.

Applies to: Flammable refrigerant units before brazing or opening circuit

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FUHA service manual, p. 6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.