Carrier · Air handler troubleshooting
Refrigerant removal, purging and evacuation
What is going on
Order of steps when breaking into the refrigerant circuit on a flammable refrigerant unit.
Check in this order
- Safely remove the refrigerant following local and national rules and recover it into correct recovery cylinders.
- Evacuate the circuit.
- Purge the circuit with oxygen-free nitrogen.
- Evacuate again.
- Flush or purge with nitrogen continuously when using flame to open the circuit, then open the circuit.
- Never use compressed air or oxygen for purging.
- Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
- Repeat the nitrogen purge until no refrigerant remains, then vent to atmospheric pressure before work.
Applies to: D5FUHAQ refrigerant circuit
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHAQ Owner's Manual, p. 5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.