What is going on

Order of steps when breaking into the refrigerant circuit on a flammable refrigerant unit.

Check in this order

  1. Safely remove the refrigerant following local and national rules and recover it into correct recovery cylinders.
  2. Evacuate the circuit.
  3. Purge the circuit with oxygen-free nitrogen.
  4. Evacuate again.
  5. Flush or purge with nitrogen continuously when using flame to open the circuit, then open the circuit.
  6. Never use compressed air or oxygen for purging.
  7. Keep the vacuum pump outlet away from ignition sources and make sure there is ventilation.
  8. Repeat the nitrogen purge until no refrigerant remains, then vent to atmospheric pressure before work.

Applies to: D5FUHAQ refrigerant circuit

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHAQ Owner's Manual, p. 5. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.