Carrier · Air handler troubleshooting

Refrigerant recovery and decommissioning

D5FSAAH / D5FLAAH

What is going on

Steps for removing refrigerant before service or disposal on a flammable refrigerant system.

Check in this order

  1. Isolate the system electrically and confirm electrical power is available before starting.
  2. Pump down the system if possible. If a vacuum is not possible, use a manifold to remove refrigerant from several points.
  3. Use recovery equipment and cylinders rated for flammable refrigerant, with a calibrated scale to check the cylinder weight.
  4. Do not fill cylinders above 80% liquid volume or exceed their maximum working pressure.
  5. Do not mix refrigerants in recovery units or cylinders.
  6. Purge with oxygen-free nitrogen only. Never use compressed air or oxygen.
  7. Label the equipment as decommissioned and as containing flammable refrigerant.

Applies to: R454B systems being serviced or decommissioned

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FS(L)AAH owner's manual, pp. 6-7. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.