Carrier · Air handler troubleshooting

Refrigerant leak sensor (flammable refrigerant units)

D5FUHAQ

What is going on

Units fitted with a refrigerant sensor shut down the outdoor compressor on a leak and run the indoor fan. The sensor has a 15 year service life and cannot be repaired.

Likely causes

  • Refrigerant sensor detects leaked flammable refrigerant
  • Sensor has reached end of service life or is faulty (display shows FHCC)

Check in this order

  1. Keep the unit powered, except during service, so the leak detection system stays active.
  2. If the indoor unit buzzes and shows a leak code, treat it as a refrigerant leak and find the source before restarting.
  3. Confirm the outdoor compressor is stopped and the indoor fan is running as expected for a leak event.
  4. If the display shows FHCC, the sensor is faulty.
  5. Replace the sensor only with the manufacturer-specified sensor. Do not repair it.

Applies to: D5FUHAQ indoor units with refrigerant sensor

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHAQ Owner's Manual, p. 4. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.