Refrigerant leak sensor (flammable refrigerant units)
What is going on
Units fitted with a refrigerant sensor shut down the outdoor compressor on a leak and run the indoor fan. The sensor has a 15 year service life and cannot be repaired.
Likely causes
- Refrigerant sensor detects leaked flammable refrigerant
- Sensor has reached end of service life or is faulty (display shows FHCC)
Check in this order
- Keep the unit powered, except during service, so the leak detection system stays active.
- If the indoor unit buzzes and shows a leak code, treat it as a refrigerant leak and find the source before restarting.
- Confirm the outdoor compressor is stopped and the indoor fan is running as expected for a leak event.
- If the display shows FHCC, the sensor is faulty.
- Replace the sensor only with the manufacturer-specified sensor. Do not repair it.
Applies to: D5FUHAQ indoor units with refrigerant sensor
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHAQ Owner's Manual, p. 4. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.