Carrier · Air handler troubleshooting
Refrigerant leak detection and repair precautions
What is going on
Safety steps when a refrigerant leak is suspected on a flammable refrigerant system.
Likely causes
- Suspected refrigerant leak on R454B system
Check in this order
- Remove or extinguish all open flames before checking for a leak.
- Do not use a halide torch or any naked-flame detector to find leaks.
- Use a leak detector suitable for flammable refrigerants and calibrated in a refrigerant-free area. Set it to no more than 25% of the LFL.
- Bubble or fluorescent leak detection fluids may be used. Do not use chlorine-based detergents.
- If brazing is needed, recover all refrigerant or isolate the leaking section with shut-off valves before starting work.
- Ventilate the area before breaking into the system or doing hot work. Keep a dry powder or CO2 extinguisher nearby.
- Follow the manufacturer's service procedures and use only manufacturer-approved parts.
Applies to: R454B refrigerant circuit
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Carrier D5FS(L)AAH owner's manual, pp. 5-6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.