Carrier · Air handler troubleshooting
Refrigerant leak detected by the leak detection system
What is going on
Response of the unit when the refrigerant sensor detects a leak. The manual does not list the leak alarm code shown on the display.
Check in this order
- Expect the indoor unit to show an error code and buzz.
- Expect the outdoor compressor to stop immediately and the indoor fan to run.
- Keep the unit powered, except during service, so the leak detection system works.
- Ventilate the area before breaking into the system or doing any hot work.
- Remove or extinguish all open flames and ignition sources.
- Check the area with a leak detector suitable for flammable refrigerants.
- If a leak needs brazing, recover all refrigerant or isolate the leaking section with shut-off valves first.
Applies to: D5FULA crossover evaporator coil with flammable refrigerant and refrigerant sensor
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FULA installation instructions, p. 5-6. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.