R454B room size and refrigerant charge limits

D5FULA

What is going on

With R454B (mildly flammable, A2L) refrigerant, the total system charge must not exceed the maximum allowed for the room area served. Ducted systems use the total conditioned area connected by ducts. The air outlet height and the minimum opening area for connected rooms also affect compliance.

Check in this order

  1. Calculate the actual system refrigerant charge Mc.
  2. Find the total conditioned area served by the ducts (TA) and the room where the unit is installed.
  3. Check the room area is at least 20% of TAmin.
  4. Check the outlet height and look up the allowed maximum charge and minimum opening area in the room-size table.
  5. If openings are needed, keep at least 50% of Anvmin below 200 mm (8 in) from the floor and add a second opening at least 1.5 m (4.9 ft) high.

Applies to: Ducted R454B coil installs

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FULA installation instructions, p. 9-10. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.