Carrier · Air handler troubleshooting

Pressure and vacuum test of field refrigerant piping

D5FUHA

What is going on

Test field-made piping after installation and before charging. Use inert gas for the pressure test and then vacuum test. Test the indoor side joints for leaks as well.

Check in this order

  1. Pressure test the low side at its design pressure and the high side at its design pressure. If the sides cannot be isolated, test the whole system at the low side design pressure.
  2. Hold the test pressure for at least 1 hour after removing the pressure source. The gauge must show no drop. Gauge resolution must not exceed 5% of test pressure.
  3. Evacuate the system. Isolate it from the pump. The pressure must not rise above 1500 microns within 10 minutes.
  4. Reach a vacuum of 500 microns or less, or the lower value required by local and national codes.
  5. Test indoor field joints with a sensitivity of 5 g/year or better at a minimum of 0.25 times maximum allowable pressure. No leak is allowed.
  6. Pressure test with oxygen-free nitrogen before recharging, and leak test after charging and before leaving the site.

Applies to: Split system field piping

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHA Installation Instructions, p. 6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.