Carrier · Air handler troubleshooting
Leak detection on flammable refrigerant joints
What is going on
Methods allowed for finding refrigerant leaks on A2L flammable refrigerant systems.
Check in this order
- Test joints with leak detection equipment rated at 1/8 oz (5 g) per year or better, with the system at standstill and under operation.
- Never use a flame or halide torch to find a leak.
- Use only leak detectors suitable for flammable refrigerant. Calibrate them in a refrigerant-free area and set them to no more than 25% of LFL.
- Bubble or fluorescent leak detection fluids are acceptable.
- If a leak needs brazing, first recover the refrigerant or isolate that section with shut-off valves.
Applies to: D5FUHAQ refrigerant circuit
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHAQ Owner's Manual, p. 5. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.