Carrier · Air handler troubleshooting

Leak detection and refrigerant removal for flammable refrigerant

D5FSAA / D5FLAA

What is going on

Leak check and removal method when opening the circuit.

Check in this order

  1. Never use a halide torch or any naked flame to search for leaks.
  2. Electronic detectors can be used, but sensitivity may need re-calibration for flammable refrigerant. Calibrate in a refrigerant-free area.
  3. Use leak detection fluid, but avoid chlorine-based detergents that can corrode copper.
  4. If a leak needs brazing, remove all refrigerant or isolate the leaking section with shut-off valves first.
  5. Remove the refrigerant per local rules and evacuate.
  6. Purge with oxygen-free nitrogen (never compressed air or oxygen), repeat as needed, then vent to atmospheric pressure before opening the circuit.
  7. Keep vacuum pump outlet away from ignition sources and make sure there is ventilation.

Applies to: Indoor and outdoor units using flammable refrigerant

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Carrier D5FSAAH / D5FLAAH installation manual, p. 8-9. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.