Carrier · Air handler troubleshooting
Furnace control signal connection
What is going on
Thermostat and furnace control wiring for the coil interface (non-communicating furnace control).
Check in this order
- Connect R to the furnace 24 VAC output and C to the common wire.
- Connect OW1 to the furnace first-stage heat (W1). If the furnace has only W, connect OW1 to W and leave OW2 unconnected.
- Connect OW2 to second-stage heat (W2). OW2 cannot be on unless OW1 is already on.
- Connect OG to the furnace G terminal. If the furnace has no G, connect OG to Y or Y1.
- Connect OY1 to furnace Y for cooling/heat pump fan speed. For 2-speed systems, connect OY1 to Y1.
- Connect OY2 to furnace Y2 for high fan speed; leave OY2 unconnected if not used with OY1 as Y.
- Use 24 V thermostat or full communication wiring per the wiring nameplate and Fig. 27 and 28.
- Do not use 24V communication between the interface and outdoor unit; use RS-485 or the included controller.
Applies to: D5FULA
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FULA installation instructions, p. 31. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.