Carrier · Air handler troubleshooting
Flare refrigerant line connections
What is going on
Procedure for cutting, deburring, flaring and tightening the copper refrigerant lines at the indoor unit. Flare nuts must be placed on the pipe before flaring because they cannot be fitted after the flare is made.
Likely causes
- Burrs or an oblique cut can break the air-tight seal
- Over-tightening can damage the bell mouth and under-tightening leaks
Check in this order
- Measure the distance between the indoor and outdoor units and cut the pipe slightly longer, square to 90 degrees.
- Remove all burrs with a reamer or deburring tool while holding the pipe pointing down.
- Seal the pipe ends with PVC tape until flaring.
- Place the flare nuts on both ends facing the correct direction.
- Clamp the flare block so the pipe end extends past the form, then flare to the dimensions in the flare table.
- Inspect the flare for cracks and even shape.
- Connect the low-pressure (gas) line first on the outdoor side, then the high-pressure line; connect outdoor pipes first, then indoor.
- Apply a thin coat of refrigeration oil to the flared ends.
- Align the centers of the two pipes and tighten the nut by hand.
- Hold the unit fitting with a backup wrench and tighten with a torque wrench to the value in the torque table.
- Use a backup wrench on both connecting and disconnecting.
Applies to: D5FUHA indoor unit, 3/8 in liquid and 3/4 in gas lines
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHA installation instruction, p. 27-28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.