Carrier · Air handler troubleshooting
Electrical control box removal
What is going on
Procedure to remove the electric control box subassembly and the boards it holds. Anti-static gloves must be worn.
Check in this order
- Remove the 4 screws of the upper cover plate assembly and remove the plate.
- Remove 3 screws and unplug the plugs.
- Pull out the electric control box subassembly.
- Unplug the power cord and remove the electric control box subassembly.
- Unplug the wires.
- Release 2 clips and remove the data transfer module control board.
- Release 3 clips and remove the installation plate for the main board.
- Unplug the wires.
- Release 2 clips and remove the main control board subassembly.
- Remove 2 screws and remove the transformer.
- Remove 4 screws and remove the installation plate.
- Remove the fan drive board.
Applies to: D5FUHA air handler electrical control box
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUHA service manual, p. 42-44. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.