Duct connections and installation direction
What is going on
Duct design drives most comfort and noise problems on combination systems. Select the orientation and drain pan before setting the unit.
Check in this order
- Use flexible duct collars to limit vibration and noise into the space.
- Insulate duct that runs through unconditioned space during cooling season, and use a vapor barrier on that insulation.
- Size the supply connection with a transition that matches the unit opening.
- Suspend ducts on flexible hangers. Do not fasten them directly to the structure.
- Add sound absorbing liner inside short return ducts or where noise may be a problem.
- Do not use this unit for non-ducted (freeblow) applications.
- Build and install duct work according to local and national codes.
- Choose vertical (up or down) or horizontal (left or right) orientation.
- For horizontal installation, install a secondary drain pan (not supplied). Keep at least 5 in (127 mm) between the bottom of the air handler and the secondary pan for proper drainage.
- Install a field-fabricated secondary drain pan with a drain to the outside wherever the unit sits over finished living space or any area that could be damaged by overflow. Some local codes require a secondary pan for any horizontal installation.
- Vertical up and horizontal left do not require changing the evaporator direction.
Applies to: D5FUAA sizes 18K to 60K
More air handler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: D5FUAA installation instructions, p. 17. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.