Carrier · Air handler troubleshooting

Decommissioning and refrigerant recovery

D5FUHAQ

What is going on

Steps for recovering refrigerant and decommissioning a flammable refrigerant unit.

Check in this order

  1. Make sure the technician knows the equipment, and take an oil and refrigerant sample if analysis may be needed.
  2. Isolate the system electrically and make sure power is available.
  3. Pump the system down if possible. If not, use a manifold to recover from several points.
  4. Place the cylinder on scales before recovery.
  5. Run the recovery machine per its instructions.
  6. Do not fill cylinders above 80% of volume as liquid, and never exceed the cylinder maximum working pressure.
  7. Evacuate compressors or compressor oil to an acceptable level before removing them. Do not heat the compressor body with an open flame.
  8. Do not reuse recovered refrigerant in another system unless it is cleaned and checked.
  9. Label the equipment as decommissioned and emptied, with date and signature, and keep the flammable refrigerant label on it.

Applies to: D5FUHAQ units being serviced or retired

More air handler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: D5FUHAQ Owner's Manual, p. 6. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.